FaultDisplayPossible Actions
SystemNo Utility1. No grid voltage. Check the grid voltage by multi-meter.
2. Check grid connection, such as wire and connector to the inverter.
3. Check breaker between inverter and grid; if it is tripped, DO NOT CLOSE again, get in touch with SAE Group as soon as possible.
SystemGrid Fault1. Wait for grid power to return to normal. If the grid returns to normal, the inverter will start again automatically within 5 minutes.
2. Check the grid voltage and frequency by multi-meter. Make sure grid voltage and frequency meet the specifications.
3. If you need any assistance or advice, get in touch with SAE Group.
SystemImpedance Fault1. The grid impedance is higher than the permissible value.
2. Wait for grid power to return to normal. If the grid returns to normal, inverter will start again automatically within 5 minutes.
3. Check the wires between inverter and grid. For high impedance connections, get an electrician to increase the wire size.
4. If you need any assistance or advice, get in touch with SAE Group.
SystemIsolation Fault1. Check the impedance between PV (+) & PV (-) and earth ground. The impedance must be larger than 8M. If the impedance is low a ground fault may exist in the PV array or wiring. Contact your PV array service provider or electrician.
2. If above actions do not fix the problem, the isolation detection circuit may be faulty. Contact SAE Group for assistance.
SystemGround Fault1. This is caused by too high ground current.
2. Disconnect the inverter from the grid power. Check the AC wiring and connection system.
3. After the cause is cleared, reconnect the grid power. Check the status of the inverter.
4. If above actions do not fix the problem, the GFCI circuit may be faulty. If you need any assistance, get in touch with SAE Group.
Inverter FailureOver Temperature1. The internal temperature is higher than specified normal value.
2. Reduce the ambient temperature by shading or ventilation improvements or move inverter to cooler place.
3. If this is not effective, a temperature sensor may be faulty. If you need any assistance, get in touch with SAE Group.
Inverter FailurePV Over Voltage1. Check the PV open-circuit voltage. This should be less than 500VDC.
2. If the PV voltage is much less than 500VDC (e.g. <430V), measure the DCV by multi-meter, compare the readings on meter and LCD. If the readings differ by >5%, get in touch with SAE Group.
Inverter FailureDevice Fault1. This is caused by an inverter malfunction.
2. Disconnect PV (+) or PV (-) from the input, start the unit again.
3. If you need any assistance or advice, get in touch with SAE Group.
Inverter FailureConsistent or Mismatch Fault1. This is caused by an inverter malfunction.
2. Disconnect PV (+) or PV (-) from the input, start the unit again.
3. If you need any assistance or advice, get in touch with SAE Group.

 

Error MessageExplanation
No UtilityGrid voltage is not detected
PV Over VoltagePV voltage is too high
DC Bus HighInternal DC bus voltage is too high
DC Bus LowInternal DC bus voltage is too low
Over TemperatureInternal temperature is too high
Grid FaultGrid voltage or frequency is out of range
Device FaultInternal fault with inverter circuits
Isolation FaultPV panel ground isolation problem
Impedance FaultGrid impedance fault (or grid disconnected)
Ground FaultGrid output ground leakage current too high
Relay FailureGrid output relay failure
DC INJ HighGrid DC injection too high
Ref 2.5V Fault2.5V reference voltage internal circuit fault
DC Sensor FaultGrid DC current sensor internal fault
GFCI FaultGround fault current interrupt fault
SCI FaultInternal Master/Slave communication fault
Consistent FaultInternal Master/Slave value mismatch fault
CPU Ver MismatchInternal Master/Slave firmware incompatible
EEPROM FaultInternal non-volatile memory fault
Grid V MismatchInternal Master/Slave grid voltage mismatch
Grid F MismatchInternal Master/Slave grid frequency mismatch
Grid Z MismatchInternal Master/Slave grid impedance mismatch
GFCI MismatchInternal Master/Slave ground fault value mismatch
DC Curr MismatchInternal Master/Slave grid DC current mismatch

Clenergy SPH Solar Inverter Slave Flash Error
Clenergy SPH Solar Inverter SCI Fault
Clenergy SPH Solar Inverter Error Messages
Clenergy Solar Inverter Low Power Output
Clenergy SPH Solar Inverter Blank Screen

 